| S1 | Root Cause Analysis | A · UCA root cause | Outdated process model: Door signal is not plausibility checked. | Door monitoring ↔ cell control ↔ robot | Conservative safe state in case of diagnostic error; intentional restart. | Validation: Inject door change, signal loss and sequence error; 100 repetitions per case. Responsible: Automation, 30.10.2026; independent safety review. | SC1: No restart without confirmed safe conditions; check measurement times against approved safety requirements. |
| S2 | UCA2 | A · UCA root cause | Door closed is confused with hazardous area clear. | Door monitoring ↔ cell control ↔ robot | Conservative safe state in case of diagnostic error; intentional restart. | Validation: Inject door change, signal loss and sequence error; 100 repetitions per case. Responsible: Automation, 30.10.2026; independent safety review. | SC1: No restart without confirmed safe conditions; check measurement times against approved safety requirements. |
| S3 | UCA3 | A · UCA root cause | Acknowledgment and door signal are evaluated in the wrong order. | Door monitoring ↔ cell control ↔ robot | Conservative safe state in case of diagnostic error; intentional restart. | Validation: Inject door change, signal loss and sequence error; 100 repetitions per case. Responsible: Automation, 30.10.2026; independent safety review. | SC1: No restart without confirmed safe conditions; check measurement times against approved safety requirements. |
| S4 | UCA4 | A · UCA root cause | Signal loss is interpreted as unchanged release status. | Door monitoring ↔ cell control ↔ robot | Conservative safe state in case of diagnostic error; intentional restart. | Validation: Inject door change, signal loss and sequence error; 100 repetitions per case. Responsible: Automation, 30.10.2026; independent safety review. | SC1: No restart without confirmed safe conditions; check measurement times against approved safety requirements. |